Six gases such as SF6 gas have been listed as emission-limiting gases under the Kyoto Protocol.
According to expert research, the greenhouse effect of SF6 gas is 23,900 times that of CO2 gas, and its life can be up to 3,200 years after being discharged into the atmosphere. However, due to its excellent electrical arc extinguishing and insulating properties, SF6 is still widely used in medium- and high-voltage power equipment.
The RGA-12 gas-insulated switchgear is insulated with pure nitrogen, truly realizing the environmental protection requirement.
For on-site replacement of the installed switchgear cabinets, the individual cabinet can be withdrawn directly without moving the installed cabinets on both sides.
With higher cost performance, the vacuum circuit breaker and three-position switch can be installed into the gas tank after commissioning is completed.
No. | Name | Parameter | Unit | ||
1 | Rated voltage | 12 | kV | ||
2 | Power frequency withstanding voltage (phase-to-phase & phase-to-earth/fracture) | 42/48 | kV | ||
3 | Lightning impulse withstanding voltage (phase-to-phase & phase-to-earth/fracture) | 75/85 | kV | ||
4 | Partial discharge (whole cabinet/components) | ≤10/≤3 | pC | ||
5 | Rated frequency | 50 | Hz | ||
6 | Rated current of main bus | 1250 | A | ||
7 | Rated current of branch bus | 1250 | A | ||
8 | Rated current of branch bus | 25 | 31.5 | kA | |
9 | Rated short-circuit making current (peak) | 63 | 80 | kA | |
10 | Rated short-time withstanding current/duration | 25/4 | 31.5/4 | kA/s | |
11 | Rated peak withstanding current | 63 | 80 | kA | |
12 | Single/back-to-back capacitor bank switching current | 630/400 | A | ||
13 | Single/back-to-back capacitor bank switching current | 5 | 次 | ||
14 | Rated operation sequence | O-0.3s-CO-180s-CO | |||
15 | Rated filling pressure | 0.13 | MPa | ||
16 | Alarm pressure | 0.11 | MPa | ||
17 | Min. functional pressure | 0.1 | MPa | ||
18 | Annual gas leakage rate | ≤0.05 | %/Y | ||
19 | Ingress protection rating | Gas tank | IP67 | / | |
Cabinet | IP41 | / | |||
20 | Rated voltage of auxiliary circuit | DC110,DC220或AC110,AC220 | V | ||
21 | Power frequency withstanding voltage (1min) of auxiliary circuit | 2 | kV | ||
22 | Weight | 600~800 | kg | ||
23 | Overall dimensions (W×D×H) | 500×1210×2250 | mm |
Note: Insulation, breaking and making are permitted under the condition of zero gauge pressure.
No | Name | Unit | Parameter | ||
1 | Rated voltage | kV | 12 | ||
2 | Operating environment of circuit breaker | Insulating gas | N2 | ||
3 | Rated operating pressure (absolute), 20℃ | MPa | 0.13 | ||
4 | Rated insulation level (in gas) | Power frequency withstanding voltage (1min) (phase-to-phase & phase-to-earth/fracture) | kV | 42/48 | |
Lightning impulse withstanding voltage (peak) (phase-to-phase & phase-to-earth/fracture) | kV | 75/85 | |||
5 | Rated frequency | Hz | 50 | ||
6 | Rated current | A | 1250 | ||
7 | Temperature rise test | A | 1.1*1250A | ||
8 | Rated short-circuit breaking current | kA | 25 | 31.5 | |
9 | Rated short-time withstanding current/duration | kA/s | 25/4 | 31.5/4 | |
10 | Rated short-circuit making current (peak) | kA | 63 | 80 | |
11 | Rated peak withstanding current | kA | 63 | 80 | |
12 | Loss of service continuity category | LSC2 | |||
13 | Closing bounce time | ms | ≤2 | ||
14 | Opening non-synchronism | ms | ≤2 | ||
15 | Closing non- synchronism | ms | ≤2 | ||
16 | Closing speed (6~0mm) | m/s | 0.7±0.2 | ||
17 | Opening speed (0~6mm) | m/s | 1.1±0.2 | ||
18 | Closing time | ms | 30~70 | ||
19 | Opening time | ms | 20~50 | ||
20 | Rated operation sequence | O-0.3s-CO-180s-CO | |||
21 | Mechanical life | Mechanical life | M2 | ||
22 | Electrical life | Mechanical life | E1 | ||
23 | Single/back-to-back capacitor bank switching current | A | 630/400 | ||
24 | Rated voltage of auxiliary circuit | V | DC110,DC220 or AC110,AC220 | ||
25 | Power frequency withstanding voltage (1min) of auxiliary circuit | kV | 2 | ||
26 | Rated power of energy storage motor | W | 90 | ||
27 | Rated power of closing coil | VA | 196 | ||
28 | Rated power of opening coil | VA | 196 |
Note: Insulation, breaking and making are permitted under the condition of zero gauge pressure.