RGA-12 Indoor Environment-Friendly Gas-Insulated Metal-Enclosed Switchgear (C-GIS)

Performance Overview

Meeting relevant Chinese standards GB3906, GB/T11022, DL/T593 and DL/T404, etc. and international standards IEC62271-200 and IEC62271-100, etc.;
Environment-friendly: Non-polluting pure N2 gas is used;
Compact structure: With the typical cabinet width of not more than 500mm, the 12kV switchgear has small cabinet size and footprint;
The switchgear is metal-armored and gas-sealed, and the high-voltage components are waterproof and dustproof with the ingress protection rating of IP67, so that they are not affected by the environment, and are completely maintenance-free;
The spring operating mechanism is adopted for the circuit breaker, and the vacuum interrupter for solid-sealed pole is used so that parts and components are greatly reduced;
The direct-acting three-position switch has manual and electric operation functions;
With modular gas tank structure, an appropriate combination scheme can be selected according to needs to ensure reliable and economic operation of the switchgear;
The intelligent control and protection units are adopted, and control, protection, measurement and communication functions are possessed, fully realizing the requirements of distribution network automation;
The reliable mechanical & electrical interlock design scheme can effectively prevent misoperation;
The bus connector is used between switchgear cabinets to achieve easy installation and flexible expansion, and no gas system processing is involved;
Manufacturing technology: Laser welding, laser cutting and helium leakage detection ensure safe operation of the equipment;
Technology: The new layout, insulation optimization design and comprehensive electric field optimization design make the field strength uniform and component distribution reasonable, and the components to reduce the electric field are used; serious consideration is given to design, materials and manufacturing processes, and rigorous theoretical demonstration and detailed physical experiments are conducted; performance indexes such as volume, structure, maintenance, safety and environmental adaptability are comprehensively considered so as to optimize the product design;

Product Features

    • Environment-friendly

      Six gases such as SF6 gas have been listed as emission-limiting gases under the Kyoto Protocol.

      According to expert research, the greenhouse effect of SF6 gas is 23,900 times that of CO2 gas, and its life can be up to 3,200 years after being discharged into the atmosphere. However, due to its excellent electrical arc extinguishing and insulating properties, SF6 is still widely used in medium- and high-voltage power equipment.

      The RGA-12 gas-insulated switchgear is insulated with pure nitrogen, truly realizing the environmental protection requirement.

    • Withdrawable intermediate cabinets

      For on-site replacement of the installed switchgear cabinets, the individual cabinet can be withdrawn directly without moving the installed cabinets on both sides.

    • Fully modular design

      With higher cost performance, the vacuum circuit breaker and three-position switch can be installed into the gas tank after commissioning is completed.

Main Technical Parameters

Technical parameter table of switchgear
No. Name Parameter Unit
1 Rated voltage 12 kV
2 Power frequency withstanding voltage (phase-to-phase & phase-to-earth/fracture) 42/48 kV
3 Lightning impulse withstanding voltage (phase-to-phase & phase-to-earth/fracture) 75/85 kV
4 Partial discharge (whole cabinet/components) ≤10/≤3 pC
5 Rated frequency 50 Hz
6 Rated current of main bus 1250 A
7 Rated current of branch bus 1250 A
8 Rated current of branch bus 25 31.5 kA
9 Rated short-circuit making current (peak) 63 80 kA
10 Rated short-time withstanding current/duration 25/4 31.5/4 kA/s
11 Rated peak withstanding current 63 80 kA
12 Single/back-to-back capacitor bank switching current 630/400 A
13 Single/back-to-back capacitor bank switching current 5
14 Rated operation sequence O-0.3s-CO-180s-CO
15 Rated filling pressure 0.13 MPa
16 Alarm pressure 0.11 MPa
17 Min. functional pressure 0.1 MPa
18 Annual gas leakage rate ≤0.05 %/Y
19 Ingress protection rating Gas tank IP67 /
Cabinet IP41 /
20 Rated voltage of auxiliary circuit DC110,DC220或AC110,AC220 V
21 Power frequency withstanding voltage (1min) of auxiliary circuit 2 kV
22 Weight 600~800 kg
23 Overall dimensions (W×D×H) 500×1210×2250 mm

Note: Insulation, breaking and making are permitted under the condition of zero gauge pressure.

Technical Parameter List of Vacuum Circuit Breaker
No Name Unit Parameter
1 Rated voltage kV 12
2 Operating environment of circuit breaker Insulating gas N2
3 Rated operating pressure (absolute), 20℃ MPa 0.13
4 Rated insulation level (in gas) Power frequency withstanding voltage (1min) (phase-to-phase & phase-to-earth/fracture) kV 42/48
Lightning impulse withstanding voltage (peak) (phase-to-phase & phase-to-earth/fracture) kV 75/85
5 Rated frequency Hz 50
6 Rated current A 1250
7 Temperature rise test A 1.1*1250A
8 Rated short-circuit breaking current kA 25 31.5
9 Rated short-time withstanding current/duration kA/s 25/4 31.5/4
10 Rated short-circuit making current (peak) kA 63 80
11 Rated peak withstanding current kA 63 80
12 Loss of service continuity category LSC2
13 Closing bounce time ms ≤2
14 Opening non-synchronism ms ≤2
15 Closing non- synchronism ms ≤2
16 Closing speed (6~0mm) m/s 0.7±0.2
17 Opening speed (0~6mm) m/s 1.1±0.2
18 Closing time ms 30~70
19 Opening time ms 20~50
20 Rated operation sequence O-0.3s-CO-180s-CO
21 Mechanical life Mechanical life M2
22 Electrical life Mechanical life E1
23 Single/back-to-back capacitor bank switching current A 630/400
24 Rated voltage of auxiliary circuit V DC110,DC220 or AC110,AC220
25 Power frequency withstanding voltage (1min) of auxiliary circuit kV 2
26 Rated power of energy storage motor W 90
27 Rated power of closing coil VA 196
28 Rated power of opening coil VA 196

Note: Insulation, breaking and making are permitted under the condition of zero gauge pressure.