SF6 Gas-Insulated Metal-Enclosed Switchgear

Performance Overview

Meeting Chinese standards GB/T3906, GB/T11022, DL/T593 and DL/T404, etc. and international standards IEC62271-100 and IEC62271-200;

With SF6 gas insulation plus vacuum breaking solution, the advantageous combination brings high comprehensive performance;

The primary circuit is gas-sealed, and the high-pressure components are not affected by altitude, are completely maintenance-free, and are highly adaptable to the environment;

With small cabinet dimensions, the compact switchgear has low layout space requirements;

The product can be applied to power grids, industrial and mining enterprises, rail transportation, commercial buildings and other usage scenarios.

Product Features

    • With modular gas tank structure, a corresponding switch configuration scheme can be selected according to function needs so as to ensure reliable and economic product;

    • The modular spring operating mechanism is adopted for the circuit breaker, and the main circuit is of solid-sealed pole structure, achieving a high degree of integration with a small number of components;

    • With double operation holes, the three-position switch has manual and electric operation modes;

    • The mechanical & electrical interlock is well-designed to effectively prevent misoperation and ensure the safety of operation and maintenance;

    • The bus connector is used between switchgear cabinets to achieve easy installation and flexible expansion, and no gas system processing is involved;

    • First-class manufacturing technology: Laser welding, CNC equipment, large stamping and helium leakage detection;

    • The high-quality production processes are strictly implemented to ensure safe and reliable operation of the switchgear.

Main Technical Parameters

No. Item Name Technical Requirement Unit
1 Rated voltage 40.5 kV
2 Power frequency withstanding voltage (phase-to-phase & phase-to-earth/fracture) 95/118 kV
3 Lightning impulse withstanding voltage 185/215 kV
4 Partial discharge test (whole cabinet/components) ≤20/3 pC
5 Rated frequency 50 Hz
6 Rated current of main bus 1250/2500 A
7 Rated current of branch bus 1250/2500 A
8 Rated short-circuit breaking current 31.5 kA
9 Rated short-circuit making current (peak) 80 kA
10 Rated short-time withstanding current/duration 31.5/4 kA/s
11 Rated peak withstanding current 80 kA
12 Single/back-to-back capacitor bank switching current 630/400 A
13 Grounding switch short-circuit making capacity 5 Times
14 Rated operation sequence 0-0.3s-CO-3min-CO
15 Rated filling pressure (abs, 20°C) 0.13 MPa
16 Alarm pressure (abs, 20°C) 0.11 MPa
17 Min. functional pressure (abs, 20°C) 0.10 MPa
18 Annual gas leakage rate <0.05 %/Y
19 Ingress protection rating (gas tank/whole cabinet) IP67/IP4X
20 Temperature rise performance 1.1 times A
21 Electrical life E2 Times
22 Mechanical life of circuit breaker M2 Times
23 Mechanical life of isolation/grounding switch 3000 Times
24 Internal arcing performance (switch bus compartment and cable compartment) 31.5/0.5 kA/s
25 Overall dimensions of cabinet 600(800)X1800x2300